The WELL Building Standard v2 is an international certification protocol that assesses the quality of built environments based on their impact on people's health and well-being. Structured in ten key concepts – including air, water, nutrition, movement and materials – the protocol dedicates a central role to the concept of light, recognizing its direct influence on circadian rhythms, visual comfort and cognitive performance. The Light concept of the WELL Building Standard v2 includes two mandatory prerequisites and seven optional credits. The prerequisites, without which certification cannot be obtained, are: L01 – Exposure to Light, which ensures adequate supply of natural or artificial light and information to the occupants, and L02 – Visual Lighting Design, which requires compliance with international lighting standards (EN 12464, IES, CIE) to ensure comfort and visual acuity.
The other requirements, optional but rewarding, contribute to the score necessary to reach the certification levels (Silver, Gold, Platinum). These are: L03 – Circadian Lighting (up to 3 points for EML ≥150–240), L04 – Glare Control (up to 3 points with anti-glare strategies), L05 and L06 – Daylight Access and Vision (up to 3–4 points for high SDA, daylight simulation and view quality), L07 – Visual Balance (1 point for uniformity and contrast management), L08 – Electric Light Quality (2 points, 1 for advanced color rendering and 1 for flicker control), and L09 – Occupant Control (up to 2 points for dimming systems and task lights).
In total, the theme of Light can contribute about 15–16 points to the overall WELL score: the L01–L02 prerequisites are mandatory for any certification, while obtaining the Silver, Gold and Platinum levels depends on the accumulation of optional points, which become decisive for reaching the highest thresholds. The result is an integrated approach in which light, in addition to meeting measurable lighting requirements, becomes a tool for health, well-being and sensory experience in certified spaces.
L01 Light Exposure: WELL v2 requires as a design basis that occupants receive sufficient natural and artificial light during the day. This prerequisite can be met through various strategies, for example: ensuring good exposure to daylight (p.es. at least 30% of the occupied area must be within 6 m of the external windows), maintaining a minimum ratio of glazed area to floor (e.g. ≥7% on each floor) or integrating circadian daytime lighting into the design (meeting at least Tier 1 of the L03 feature, see below). In addition, WELL v2 imposes an educational requirement: the project must include information initiatives for occupants on topics related to light and health (e.g. circadian rhythm and sleep, increased light requirement with age, importance of natural light, etc.). As L01 is a prerequisite, these design and training measures are mandatory for certification.
L02 Visual Lighting Design: This is the second prerequisite, aimed at ensuring visual comfort and adequate visual acuity for all users through artificial lighting. In practice, WELL v2 requires that the project complies with the recognized lighting standards: all spaces (indoor and outdoor) must meet the illuminance levels (lux) prescribed by reference regulatory guidelines, to be chosen from the most widespread international ones, such as the IES (Illuminating Engineering Society) standards, the EN 12464-1/2 standard (lighting of work environments), ISO 8995-1:2002 / CIE S 008 (international equivalent), the Chinese code GB50034-2013 or the CIBSE Code for Lighting. This ensures that best practice lux levels are provided for each activity. In addition, the age of the occupants and the specific visual activities performed must be taken into account, for example by providing more illuminance for precision tasks or for older users with higher visual needs. L02 also requires the drafting of a lighting plan detailing the solutions adopted for the lighting of the workstations, the heights of the worktops considered and how the design ensures the suitability of the lighting according to the age and tasks of the occupants. This alignment with established standards eliminates conflicts with local regulations and ensures a mandatory basic level of visual quality for all certified projects.
Circadian Lighting (Feature L03 – Circadian Lighting Design): This credit aims to support the circadian health of occupants by providing light of adequate intensity and quality during the day and reducing the stimulating component at night. The metric introduced by WELL to quantify the circadian effect of light is the Melanopic Equivalent Lux ( EML), which represents the illuminance weighted on the sensitivity of the non-visual photoreceptors of the human eye (the intrinsically photosensitive retinal ganglion cells, sensitive mainly to blue-cyan light around 490 nm) instead of on the cones (visual sensitivity peak at ~555 nm). In practical terms, EML is calculated as the product of the measured photopic illuminance (lux) and a melanopic ratio characteristic of the light source (called melanopic ratio, R). The latter expresses the spectral effectiveness of the source in stimulating melanopsin receptors compared to photopic vision. For example, an LED lamp with a high blue-green component will have a higher melanopic R ratio (>1) than a hot lamp with more red components. The calculation is: EML = photopic lux × melanopic R.
WELL v2 also establishes circadian illuminance thresholds that environments must reach in certain conditions of time and place. In office environments, for example, it is required to ensure in the morning (for at least 4 hours, approximately between 9:00 and 13:00) a vertical light level at the eye position of at least ~150 EML for all workstations. This value can be obtained by combining natural and artificial light; in fact, the system allows slight reductions in the electrical contribution if the environment benefits from good daylight inputs (e.g. 120 EML from artificial lighting + daylighting credits). A higher level of ~240 EML (vertical) guaranteed during daylight hours allows you to obtain the maximum score for this feature. (For reference, 240 EML corresponds to approximately 218 melanopic lux equivalent to daylight D65.) In general, light sources with high EML (on the order of 125–250) are suitable for daytime activities, while for evening/night hours, sources with very low EML (<50) are recommended to reduce circadian impact. At night, WELL requires limiting melanopic levels: for example, in bedrooms or dark environments, nighttime lighting must have less than 50 melanopic lux so as not to disturb the circadian rhythm of sleep.
Required parameters: During the performance verification, the EML is measured in the vertical plane at eye level (about 1.2 m from the ground) at the eyes of the occupants. An example of a commonly cited threshold is 250 vertical EML as the average level to be guaranteed during the day to adequately support the alertness and alignment of the biological clock. In WELL v2, as seen, the basic target is ~150 EML, with incentives for higher levels. In residential or hospital contexts, at least 200 EML is required for the day in environments such as living rooms and kitchens, and simultaneously at night very dimmed lighting (<50 EML) to promote rest.
Scientific/regulatory references: The melanopic model adopted by WELL is based on the spectral action curves proposed by Lucas et al. (2014) and subsequently formalized by the CIE (International Commission on Illumination) in the CIE S 026:2018 report. The CIE defines similar metrics (e.g. Melanopic Equivalent Daylight Illuminance - MEDI); it is useful to note that 1 EML according to WELL is equivalent to ~0.90 MEAN melanopic referred to D65 according to the CIE scale. There is also another circadian efficacy index, the Circadian Stimulus (CS) developed by the Lighting Research Center, but WELL v2 adopted the melanopic EML model.
Practical solutions: To meet these circadian requirements, designers often use tunable-white or blue-cyan enriched spectrum lighting. For example, the SkyBlue BIOS technology integrates LEDs with spectral peaks aimed at maximizing the melanopic ratio (M/P) while maintaining excellent color rendering; manufacturers such as ALW, iGuzzini, Zumtobel, Fagerhult, etc., offer luminaires with advanced circadian technology. These solutions achieve high melanopic ratio values (even >1) for a given color temperature, allowing the required melanopic lux to be achieved without having to excessively raise visual illuminance levels or use excessively cold light. For example, "biologically optimized" LEDs with high M/P ratios make it possible to meet 150–200 EML with fewer or lower intensities, while also reducing the risk of glare and maintaining pleasing colors (high CRI with R9>50).
Glare Control (Feature L04 – Glare Control): Glare, whether due to the sun or artificial lighting, is a critical factor for visual comfort. The L04 feature of WELL v2 requires minimizing the glare perceived by the occupants through a combination of design and technological strategies. As far as natural light is concerned, direct solar glare phenomena must be avoided: the project must include adequate shading systems (movable internal/external blinds, solar control glass, sunshades, etc.) or alternatively demonstrate through calculations (e.g. evaluation of solar luminance or Daylight Glare Probability) that glare is under control in all occupied spaces. Many projects choose the path of automatic solar shading that is activated when necessary, a solution that WELL also rewards in daylight credits (L05).
For artificial lighting, WELL v2 provides four design options to achieve glare-free credit, leaving flexibility to the design team. In summary, the photometric characteristics of the luminaires and the lighting layout must be addressed so that no occupant is exposed to excessively bright sources in their field of vision. Key strategies include:
L04 Glare Control allows you to achieve up to 3 optimization points and, although no longer a mandatory prerequisite in WELL v2, it is an essential component for visual comfort. Implementing one or more of the strategies described above helps to create much more comfortable working environments by reducing visual fatigue. From a product point of view, almost all major lighting manufacturers have luminaires specifically designed to minimize glare: for example, LED panels with microprisms, downlights with honeycomb shielding, indirect suspensions only, etc., many of which are explicitly advertised as compatible with WELL certification.
Daylight Access (Feature L05 & L06): WELL v2 strongly encourages daylighting design, recognizing the benefits of natural light on well-being and circadian rhythm. Features L05 (Daylight Design Strategies) and L06 (Daylight Simulation) provide up to 3-4 total points if the design excels at using natural light.
In summary, daylight credits reward buildings with large, well-calibrated glass surfaces, internal distribution that brings light deep into the depths (e.g., central atriums, skylights), use of light-diffusing materials (light walls, high ceiling reflectance), and advanced shading technologies. Many WELL-certified buildings, for example, use electrochromic glass or sensor-controlled motorized curtain systems, so as to maximize useful daylight while reducing reflections and overheating. Proper daylight design also contributes to meeting circadian criteria (reducing the need for electric light to achieve the required EMLs, as seen above).
Visual Balance (Feature L07 – Visual Balance): This optimization (1 point) addresses an often overlooked aspect: the management of light contrasts and the balanced distribution of brightness in space. The aim is to create visually comfortable environments by avoiding excessively bright areas next to areas that are too dark, which strain the eyes. WELL L07 defines precise quantitative criteria for brightness management. For example, it is required that in the various rooms the horizontal/vertical luminance ratios between adjacent areas do not exceed 10:1 if controlled separately (this avoids "spots" of light that are too concentrated). Similarly, the uniformity of illuminance on each horizontal work surface must be at least 0.4 (minimum/average ratio ≥ 40%), to prevent some desks from having brightly lit areas and others in dim light. In addition, WELL suggests paying attention to the chromatic and temporal consistency of the lighting: if dynamic lighting fixtures are used, changes in light levels or hues must occur gradually (over periods ≥ 10 minutes) so as not to be disturbing. The Correlated Color Temperature (CCT) should also be uniform between similar luminaires in the same environment, with instantaneous variations < ±200 K, to avoid uneven perceptions.
WELL allows two approaches: meet at least 3 of the proposed quantitative criteria (contrast ratio, uniformity, gradualness of variations, CCT coherence), or demonstrate through a lighting professional that the project carefully considers these aspects of visual balance in all environments. In practice, this credit incentivizes a "holistic" lighting project, in which in addition to providing adequate lux levels, light hierarchies are taken care of: for example, by also illuminating the walls or ceiling moderately (to have a balance with horizontal surfaces), avoiding strong contrasts near critical locations, and perhaps introducing varied but comfortable lighting scenarios throughout the day. A common case is the management of background brightness in offices: a bright screen on a dark background can strain the eyes, so L07 encourages illuminating the walls behind the screens at a certain level to reduce contrast. This type of design attention, already described in the literature (e.g. CIE and IES Lighting Handbook), is formalized by WELL to further improve perceived visual comfort.
Electric Light Quality (Feature L08 – Electric Light Quality): The L08 feature focuses on the spectral quality and technical performance of artificial lighting, with the aim of improving color rendering and reducing flicker phenomena of light sources. It is divided into two main parts:
In summary, L08 pushes projects to select high-quality light sources both in spectrum (high CRI/TM-30) and electronics (low flicker). This benefit translates into environments where the colors of materials, foods, plants, faces appear natural and vivid, and where artificial light is as continuous and restful as sunlight. Manufacturers publish melanopic conversion factors (for L03) for all their tunable white ranges and ensure color rendering and flicker performance that comply with WELL criteria. For example, some manufacturers provide data sheets with melanopic LED factors that follow DIN SPEC 5031-100 and CIE S 026 to help lighting designers evaluate both photopic and melanopic lux of a system. In parallel, many modern LED fixtures use high-frequency drivers (often > 2-4 kHz) and digital dimming (DALI2, etc.) with high-frequency PWM modulation or analog techniques to dramatically reduce perceived flicker, often declaring IEEE 1789 compliance. This highlights how the industry is embracing WELL requirements as new quality standards.
Occupant Control (Feature L09 – Occupant Lighting Control): The latest optimization of the Light theme in WELL v2 concerns ergonomics and customization of lighting: points are earned by offering users the ability to control and adjust their lighting environment. Individual control is proven to increase satisfaction and comfort, as everyone has different preferences in terms of light level and shade.
WELL L09 has two levels: Part 1 – Ambient Lighting Control and Part 2 – Supplementary Lighting. For the first part (up to 2 points), the project must divide the spaces into fairly small and intuitive light zones (e.g. for each large open space, private office or function area there should be at least one control zone). Indicatively, for every 30 m² of area or for each group of 10 occupants a separate zone should be provided (this is to avoid a single switch for an entire floor, for example). Each zone must have control systems that offer at least three user-selectable lighting levels or scenarios – e.g. high, medium, low light, or preset scenes for "PC work", "meeting projection", "relax" etc. In addition, it is required that it is possible to change at least one quality characteristic of the light in addition to the quantity: this can be the colour temperature (CCT), the tone (RGB colour) or the distribution (e.g. by switching on different groups of lights). In practice, a dynamic and customizable lighting system. All regular occupants must have access to these controls – physical (wall push-button panels, remote controls) or via digital interfaces (app, computer) – in a simple way and preferably in their immediate environment. For example, an open-plan office could have a wall panel and an app that allow those who work in that area to dim the lights or warm their color at will within certain limits. WELL also specifies that the lights dedicated to presentations/projections can be controlled separately, so as to dim only the screen if necessary without turning off the whole room. Meeting these requirements (zones + advanced controls) gives 1 point; if the system is also circadian automatic (i.e. it supports gradual day/night changes in line with L03) and simultaneously allows manual overriding, an additional point of integrated innovation can be achieved (this is not explicitly required but many designers implement controls that follow a predefined circadian cycle with the possibility of manual adjustment to suit both L03 and L09).
Part 2 of L09 (1 additional point) requires that individual additional lighting, e.g. personal table lamps (task lights) be made available to occupants on request. Such accent lights must be provided free of charge by the company to those who request them (with at least one demonstration unit available) and must meet certain criteria: they must be able to increase the illuminance level on the task to at least twice the general level, they must be dimmable by the user independently of the ambient lighting, and they must be positioned/swivelled at the workplace as desired. In addition, the light source of these lamps must not be exposed directly to the eyes (shielded) so as not to introduce new glare. In practice, the use of ergonomic work lamps (e.g. LED articulated arms) is encouraged that the user can turn on and adjust when performing more precise tasks, improving local lighting without disturbing others. This aspect is important in environments such as shared offices: giving local control avoids conflicts (those who prefer more light get it on their desk, without having to turn up the general lighting for everyone).
Implementing L09 demonstrates a strong "human-centric" orientation: not only is the environment designed to be of high quality, but it puts the individual at the center, allowing them to adapt the light to their needs and feelings. Many manufacturers offer advanced control systems (e.g. IoT platforms, DALI with apps, Bluetooth wireless systems) compatible with these requirements, and provide luminaires prepared for tunable white and continuous dimming. For example, solutions from Lutron, Helvar, Casambi and the like are often employed in WELL projects to create intuitive user interfaces and customizable light scenarios. Innovative table lamps are also advertised as ideal tools to meet the individual comfort required by L09.
Examples of WELL v2 Compliant Lighting Solutions
Many lighting companies have embraced the principles of the WELL Building Standard and have developed products and guidelines to facilitate their implementation. For example, Zumtobel has published a handbook dedicated to Human Centric Lighting in which it provides the melanopic factor (MELanopic factor) required to calculate melanopic lux according to CIE and WELL for each of its tunable white products . This helps lighting designers to choose the right lamps to meet L03. In its technical articles, Fagerhult emphasises the importance of the "melanopic ratio" and offers solutions for healthcare and office environments aimed at supporting the circadian rhythm of those present (e.g. systems with additional blue LEDs in the morning and warm light in the evening). iGuzzini has collaborated with the Politecnico di Milano on circadian designs: their luminaires with Twilight C technology allow the CCT to be adjusted from warm to cold white, accompanying biological cycles. Many office luminaires of these brands (e.g. Trick by iGuzzini, Mirel Evolution by Zumtobel, or Appareo by Fagerhult) are designed with high uniformity diffusers and UGR <19, meeting the anti-glare requirements of WELL. Some manufacturers (e.g. BIOS Lighting in partnership with different brands) offer specialized LED modules with very high M/P ratios, which integrated into the ceiling lights allow you to reach 240 EML with fewer fixtures and without using extreme color temperatures.
In addition, by integrating environmental sensors and automatic controls (e.g. Daylight Harvesting systems to adjust artificial light according to natural light, or circadian control units that gradually change intensity/CCT throughout the day), it becomes easier to simultaneously comply with circadian lighting (L03), energy efficiency and comfort credits. For example, the WaveLinx platform with BioUp integration has introduced the first wired and wireless lighting control system capable of seamlessly adjusting the melanopic component of light from 2700K to 5000K during the day. This shows how the market is innovating for truly human-centered lighting, providing turnkey solutions for WELL buildings.
In conclusion, the WELL Building Standard v2 – Light Concept represents one of the most advanced and comprehensive references for lighting design oriented towards human well-being. It combines quantifiable requirements (lux, EML, UGR, CRI, flicker, etc.) – often borrowed or harmonized with CIE, IES, EN standards – with a holistic approach that also embraces educational and behavioral aspects. A lighting design that meets WELL v2 guarantees bright yet comfortable indoor environments, with brighter days and darker nights to respect our circadian rhythm, free of glare or other visual stressors, and able to adapt to people's needs. Leading companies in the sector have already begun to offer products and systems in line with these criteria, facilitating the practical creation of "WELL-lit" spaces in the true sense of the word – where light becomes a tool for health and comfort, as well as visual performance.

The WELL Building Standard v2 is an international certification protocol that assesses the quality of built environments based on their impact on people's health and well-being. Structured in ten key concepts – including air, water, nutrition, movement and materials – the protocol dedicates a central role to the concept of light, recognizing its direct influence on circadian rhythms, visual comfort and cognitive performance. The Light concept of the WELL Building Standard v2 includes two mandatory prerequisites and seven optional credits. The prerequisites, without which certification cannot be obtained, are: L01 – Exposure to Light, which ensures adequate supply of natural or artificial light and information to the occupants, and L02 – Visual Lighting Design, which requires compliance with international lighting standards (EN 12464, IES, CIE) to ensure comfort and visual acuity.
The other requirements, optional but rewarding, contribute to the score necessary to reach the certification levels (Silver, Gold, Platinum). These are: L03 – Circadian Lighting (up to 3 points for EML ≥150–240), L04 – Glare Control (up to 3 points with anti-glare strategies), L05 and L06 – Daylight Access and Vision (up to 3–4 points for high SDA, daylight simulation and view quality), L07 – Visual Balance (1 point for uniformity and contrast management), L08 – Electric Light Quality (2 points, 1 for advanced color rendering and 1 for flicker control), and L09 – Occupant Control (up to 2 points for dimming systems and task lights).
In total, the theme of Light can contribute about 15–16 points to the overall WELL score: the L01–L02 prerequisites are mandatory for any certification, while obtaining the Silver, Gold and Platinum levels depends on the accumulation of optional points, which become decisive for reaching the highest thresholds. The result is an integrated approach in which light, in addition to meeting measurable lighting requirements, becomes a tool for health, well-being and sensory experience in certified spaces.
L01 Light Exposure: WELL v2 requires as a design basis that occupants receive sufficient natural and artificial light during the day. This prerequisite can be met through various strategies, for example: ensuring good exposure to daylight (p.es. at least 30% of the occupied area must be within 6 m of the external windows), maintaining a minimum ratio of glazed area to floor (e.g. ≥7% on each floor) or integrating circadian daytime lighting into the design (meeting at least Tier 1 of the L03 feature, see below). In addition, WELL v2 imposes an educational requirement: the project must include information initiatives for occupants on topics related to light and health (e.g. circadian rhythm and sleep, increased light requirement with age, importance of natural light, etc.). As L01 is a prerequisite, these design and training measures are mandatory for certification.
L02 Visual Lighting Design: This is the second prerequisite, aimed at ensuring visual comfort and adequate visual acuity for all users through artificial lighting. In practice, WELL v2 requires that the project complies with the recognized lighting standards: all spaces (indoor and outdoor) must meet the illuminance levels (lux) prescribed by reference regulatory guidelines, to be chosen from the most widespread international ones, such as the IES (Illuminating Engineering Society) standards, the EN 12464-1/2 standard (lighting of work environments), ISO 8995-1:2002 / CIE S 008 (international equivalent), the Chinese code GB50034-2013 or the CIBSE Code for Lighting. This ensures that best practice lux levels are provided for each activity. In addition, the age of the occupants and the specific visual activities performed must be taken into account, for example by providing more illuminance for precision tasks or for older users with higher visual needs. L02 also requires the drafting of a lighting plan detailing the solutions adopted for the lighting of the workstations, the heights of the worktops considered and how the design ensures the suitability of the lighting according to the age and tasks of the occupants. This alignment with established standards eliminates conflicts with local regulations and ensures a mandatory basic level of visual quality for all certified projects.
Circadian Lighting (Feature L03 – Circadian Lighting Design): This credit aims to support the circadian health of occupants by providing light of adequate intensity and quality during the day and reducing the stimulating component at night. The metric introduced by WELL to quantify the circadian effect of light is the Melanopic Equivalent Lux ( EML), which represents the illuminance weighted on the sensitivity of the non-visual photoreceptors of the human eye (the intrinsically photosensitive retinal ganglion cells, sensitive mainly to blue-cyan light around 490 nm) instead of on the cones (visual sensitivity peak at ~555 nm). In practical terms, EML is calculated as the product of the measured photopic illuminance (lux) and a melanopic ratio characteristic of the light source (called melanopic ratio, R). The latter expresses the spectral effectiveness of the source in stimulating melanopsin receptors compared to photopic vision. For example, an LED lamp with a high blue-green component will have a higher melanopic R ratio (>1) than a hot lamp with more red components. The calculation is: EML = photopic lux × melanopic R.
WELL v2 also establishes circadian illuminance thresholds that environments must reach in certain conditions of time and place. In office environments, for example, it is required to ensure in the morning (for at least 4 hours, approximately between 9:00 and 13:00) a vertical light level at the eye position of at least ~150 EML for all workstations. This value can be obtained by combining natural and artificial light; in fact, the system allows slight reductions in the electrical contribution if the environment benefits from good daylight inputs (e.g. 120 EML from artificial lighting + daylighting credits). A higher level of ~240 EML (vertical) guaranteed during daylight hours allows you to obtain the maximum score for this feature. (For reference, 240 EML corresponds to approximately 218 melanopic lux equivalent to daylight D65.) In general, light sources with high EML (on the order of 125–250) are suitable for daytime activities, while for evening/night hours, sources with very low EML (<50) are recommended to reduce circadian impact. At night, WELL requires limiting melanopic levels: for example, in bedrooms or dark environments, nighttime lighting must have less than 50 melanopic lux so as not to disturb the circadian rhythm of sleep.
Required parameters: During the performance verification, the EML is measured in the vertical plane at eye level (about 1.2 m from the ground) at the eyes of the occupants. An example of a commonly cited threshold is 250 vertical EML as the average level to be guaranteed during the day to adequately support the alertness and alignment of the biological clock. In WELL v2, as seen, the basic target is ~150 EML, with incentives for higher levels. In residential or hospital contexts, at least 200 EML is required for the day in environments such as living rooms and kitchens, and simultaneously at night very dimmed lighting (<50 EML) to promote rest.
Scientific/regulatory references: The melanopic model adopted by WELL is based on the spectral action curves proposed by Lucas et al. (2014) and subsequently formalized by the CIE (International Commission on Illumination) in the CIE S 026:2018 report. The CIE defines similar metrics (e.g. Melanopic Equivalent Daylight Illuminance - MEDI); it is useful to note that 1 EML according to WELL is equivalent to ~0.90 MEAN melanopic referred to D65 according to the CIE scale. There is also another circadian efficacy index, the Circadian Stimulus (CS) developed by the Lighting Research Center, but WELL v2 adopted the melanopic EML model.
Practical solutions: To meet these circadian requirements, designers often use tunable-white or blue-cyan enriched spectrum lighting. For example, the SkyBlue BIOS technology integrates LEDs with spectral peaks aimed at maximizing the melanopic ratio (M/P) while maintaining excellent color rendering; manufacturers such as ALW, iGuzzini, Zumtobel, Fagerhult, etc., offer luminaires with advanced circadian technology. These solutions achieve high melanopic ratio values (even >1) for a given color temperature, allowing the required melanopic lux to be achieved without having to excessively raise visual illuminance levels or use excessively cold light. For example, "biologically optimized" LEDs with high M/P ratios make it possible to meet 150–200 EML with fewer or lower intensities, while also reducing the risk of glare and maintaining pleasing colors (high CRI with R9>50).
Glare Control (Feature L04 – Glare Control): Glare, whether due to the sun or artificial lighting, is a critical factor for visual comfort. The L04 feature of WELL v2 requires minimizing the glare perceived by the occupants through a combination of design and technological strategies. As far as natural light is concerned, direct solar glare phenomena must be avoided: the project must include adequate shading systems (movable internal/external blinds, solar control glass, sunshades, etc.) or alternatively demonstrate through calculations (e.g. evaluation of solar luminance or Daylight Glare Probability) that glare is under control in all occupied spaces. Many projects choose the path of automatic solar shading that is activated when necessary, a solution that WELL also rewards in daylight credits (L05).
For artificial lighting, WELL v2 provides four design options to achieve glare-free credit, leaving flexibility to the design team. In summary, the photometric characteristics of the luminaires and the lighting layout must be addressed so that no occupant is exposed to excessively bright sources in their field of vision. Key strategies include:
L04 Glare Control allows you to achieve up to 3 optimization points and, although no longer a mandatory prerequisite in WELL v2, it is an essential component for visual comfort. Implementing one or more of the strategies described above helps to create much more comfortable working environments by reducing visual fatigue. From a product point of view, almost all major lighting manufacturers have luminaires specifically designed to minimize glare: for example, LED panels with microprisms, downlights with honeycomb shielding, indirect suspensions only, etc., many of which are explicitly advertised as compatible with WELL certification.
Daylight Access (Feature L05 & L06): WELL v2 strongly encourages daylighting design, recognizing the benefits of natural light on well-being and circadian rhythm. Features L05 (Daylight Design Strategies) and L06 (Daylight Simulation) provide up to 3-4 total points if the design excels at using natural light.
In summary, daylight credits reward buildings with large, well-calibrated glass surfaces, internal distribution that brings light deep into the depths (e.g., central atriums, skylights), use of light-diffusing materials (light walls, high ceiling reflectance), and advanced shading technologies. Many WELL-certified buildings, for example, use electrochromic glass or sensor-controlled motorized curtain systems, so as to maximize useful daylight while reducing reflections and overheating. Proper daylight design also contributes to meeting circadian criteria (reducing the need for electric light to achieve the required EMLs, as seen above).
Visual Balance (Feature L07 – Visual Balance): This optimization (1 point) addresses an often overlooked aspect: the management of light contrasts and the balanced distribution of brightness in space. The aim is to create visually comfortable environments by avoiding excessively bright areas next to areas that are too dark, which strain the eyes. WELL L07 defines precise quantitative criteria for brightness management. For example, it is required that in the various rooms the horizontal/vertical luminance ratios between adjacent areas do not exceed 10:1 if controlled separately (this avoids "spots" of light that are too concentrated). Similarly, the uniformity of illuminance on each horizontal work surface must be at least 0.4 (minimum/average ratio ≥ 40%), to prevent some desks from having brightly lit areas and others in dim light. In addition, WELL suggests paying attention to the chromatic and temporal consistency of the lighting: if dynamic lighting fixtures are used, changes in light levels or hues must occur gradually (over periods ≥ 10 minutes) so as not to be disturbing. The Correlated Color Temperature (CCT) should also be uniform between similar luminaires in the same environment, with instantaneous variations < ±200 K, to avoid uneven perceptions.
WELL allows two approaches: meet at least 3 of the proposed quantitative criteria (contrast ratio, uniformity, gradualness of variations, CCT coherence), or demonstrate through a lighting professional that the project carefully considers these aspects of visual balance in all environments. In practice, this credit incentivizes a "holistic" lighting project, in which in addition to providing adequate lux levels, light hierarchies are taken care of: for example, by also illuminating the walls or ceiling moderately (to have a balance with horizontal surfaces), avoiding strong contrasts near critical locations, and perhaps introducing varied but comfortable lighting scenarios throughout the day. A common case is the management of background brightness in offices: a bright screen on a dark background can strain the eyes, so L07 encourages illuminating the walls behind the screens at a certain level to reduce contrast. This type of design attention, already described in the literature (e.g. CIE and IES Lighting Handbook), is formalized by WELL to further improve perceived visual comfort.
Electric Light Quality (Feature L08 – Electric Light Quality): The L08 feature focuses on the spectral quality and technical performance of artificial lighting, with the aim of improving color rendering and reducing flicker phenomena of light sources. It is divided into two main parts:
In summary, L08 pushes projects to select high-quality light sources both in spectrum (high CRI/TM-30) and electronics (low flicker). This benefit translates into environments where the colors of materials, foods, plants, faces appear natural and vivid, and where artificial light is as continuous and restful as sunlight. Manufacturers publish melanopic conversion factors (for L03) for all their tunable white ranges and ensure color rendering and flicker performance that comply with WELL criteria. For example, some manufacturers provide data sheets with melanopic LED factors that follow DIN SPEC 5031-100 and CIE S 026 to help lighting designers evaluate both photopic and melanopic lux of a system. In parallel, many modern LED fixtures use high-frequency drivers (often > 2-4 kHz) and digital dimming (DALI2, etc.) with high-frequency PWM modulation or analog techniques to dramatically reduce perceived flicker, often declaring IEEE 1789 compliance. This highlights how the industry is embracing WELL requirements as new quality standards.
Occupant Control (Feature L09 – Occupant Lighting Control): The latest optimization of the Light theme in WELL v2 concerns ergonomics and customization of lighting: points are earned by offering users the ability to control and adjust their lighting environment. Individual control is proven to increase satisfaction and comfort, as everyone has different preferences in terms of light level and shade.
WELL L09 has two levels: Part 1 – Ambient Lighting Control and Part 2 – Supplementary Lighting. For the first part (up to 2 points), the project must divide the spaces into fairly small and intuitive light zones (e.g. for each large open space, private office or function area there should be at least one control zone). Indicatively, for every 30 m² of area or for each group of 10 occupants a separate zone should be provided (this is to avoid a single switch for an entire floor, for example). Each zone must have control systems that offer at least three user-selectable lighting levels or scenarios – e.g. high, medium, low light, or preset scenes for "PC work", "meeting projection", "relax" etc. In addition, it is required that it is possible to change at least one quality characteristic of the light in addition to the quantity: this can be the colour temperature (CCT), the tone (RGB colour) or the distribution (e.g. by switching on different groups of lights). In practice, a dynamic and customizable lighting system. All regular occupants must have access to these controls – physical (wall push-button panels, remote controls) or via digital interfaces (app, computer) – in a simple way and preferably in their immediate environment. For example, an open-plan office could have a wall panel and an app that allow those who work in that area to dim the lights or warm their color at will within certain limits. WELL also specifies that the lights dedicated to presentations/projections can be controlled separately, so as to dim only the screen if necessary without turning off the whole room. Meeting these requirements (zones + advanced controls) gives 1 point; if the system is also circadian automatic (i.e. it supports gradual day/night changes in line with L03) and simultaneously allows manual overriding, an additional point of integrated innovation can be achieved (this is not explicitly required but many designers implement controls that follow a predefined circadian cycle with the possibility of manual adjustment to suit both L03 and L09).
Part 2 of L09 (1 additional point) requires that individual additional lighting, e.g. personal table lamps (task lights) be made available to occupants on request. Such accent lights must be provided free of charge by the company to those who request them (with at least one demonstration unit available) and must meet certain criteria: they must be able to increase the illuminance level on the task to at least twice the general level, they must be dimmable by the user independently of the ambient lighting, and they must be positioned/swivelled at the workplace as desired. In addition, the light source of these lamps must not be exposed directly to the eyes (shielded) so as not to introduce new glare. In practice, the use of ergonomic work lamps (e.g. LED articulated arms) is encouraged that the user can turn on and adjust when performing more precise tasks, improving local lighting without disturbing others. This aspect is important in environments such as shared offices: giving local control avoids conflicts (those who prefer more light get it on their desk, without having to turn up the general lighting for everyone).
Implementing L09 demonstrates a strong "human-centric" orientation: not only is the environment designed to be of high quality, but it puts the individual at the center, allowing them to adapt the light to their needs and feelings. Many manufacturers offer advanced control systems (e.g. IoT platforms, DALI with apps, Bluetooth wireless systems) compatible with these requirements, and provide luminaires prepared for tunable white and continuous dimming. For example, solutions from Lutron, Helvar, Casambi and the like are often employed in WELL projects to create intuitive user interfaces and customizable light scenarios. Innovative table lamps are also advertised as ideal tools to meet the individual comfort required by L09.
Examples of WELL v2 Compliant Lighting Solutions
Many lighting companies have embraced the principles of the WELL Building Standard and have developed products and guidelines to facilitate their implementation. For example, Zumtobel has published a handbook dedicated to Human Centric Lighting in which it provides the melanopic factor (MELanopic factor) required to calculate melanopic lux according to CIE and WELL for each of its tunable white products . This helps lighting designers to choose the right lamps to meet L03. In its technical articles, Fagerhult emphasises the importance of the "melanopic ratio" and offers solutions for healthcare and office environments aimed at supporting the circadian rhythm of those present (e.g. systems with additional blue LEDs in the morning and warm light in the evening). iGuzzini has collaborated with the Politecnico di Milano on circadian designs: their luminaires with Twilight C technology allow the CCT to be adjusted from warm to cold white, accompanying biological cycles. Many office luminaires of these brands (e.g. Trick by iGuzzini, Mirel Evolution by Zumtobel, or Appareo by Fagerhult) are designed with high uniformity diffusers and UGR <19, meeting the anti-glare requirements of WELL. Some manufacturers (e.g. BIOS Lighting in partnership with different brands) offer specialized LED modules with very high M/P ratios, which integrated into the ceiling lights allow you to reach 240 EML with fewer fixtures and without using extreme color temperatures.
In addition, by integrating environmental sensors and automatic controls (e.g. Daylight Harvesting systems to adjust artificial light according to natural light, or circadian control units that gradually change intensity/CCT throughout the day), it becomes easier to simultaneously comply with circadian lighting (L03), energy efficiency and comfort credits. For example, the WaveLinx platform with BioUp integration has introduced the first wired and wireless lighting control system capable of seamlessly adjusting the melanopic component of light from 2700K to 5000K during the day. This shows how the market is innovating for truly human-centered lighting, providing turnkey solutions for WELL buildings.
In conclusion, the WELL Building Standard v2 – Light Concept represents one of the most advanced and comprehensive references for lighting design oriented towards human well-being. It combines quantifiable requirements (lux, EML, UGR, CRI, flicker, etc.) – often borrowed or harmonized with CIE, IES, EN standards – with a holistic approach that also embraces educational and behavioral aspects. A lighting design that meets WELL v2 guarantees bright yet comfortable indoor environments, with brighter days and darker nights to respect our circadian rhythm, free of glare or other visual stressors, and able to adapt to people's needs. Leading companies in the sector have already begun to offer products and systems in line with these criteria, facilitating the practical creation of "WELL-lit" spaces in the true sense of the word – where light becomes a tool for health and comfort, as well as visual performance.
Other Lighting Post
Other Lighting Post
This section brings together a comprehensive body of theoretical, scientific, and design insights into the theory of light applied to lighting design, systematically addressing the complex relationship between light, visual perception, and spatial design. The content develops the physical foundations of light, an understanding of the mechanisms of human vision, the differences between photopic and melanopic illuminance, and the biological impact of artificial light, integrating advanced metrics and contemporary interpretation criteria.
The page also explores the functioning of LED sources, the spectral and perceptual implications of solid-state light, the evolution of color rendering criteria, and the growing role of light as an informational and perceptual system, capable of influencing behavior, comfort, and the quality of spatial experience.
Ample space is dedicated to the relevant regulatory and technical framework, international standards, sustainability protocols, and control systems, understood as essential tools for rigorous, measurable, and consistent design.
Overall, the section provides a vision of the theory of light as the cultural and operational basis of lighting design, in which scientific knowledge, perceptual awareness, and design method converge to guide the lighting designer in the construction of balanced, legible, and qualitatively significant spaces.
This section brings together a comprehensive body of theoretical, scientific, and design insights into the theory of light applied to lighting design, systematically addressing the complex relationship between light, visual perception, and spatial design. The content develops the physical foundations of light, an understanding of the mechanisms of human vision, the differences between photopic and melanopic illuminance, and the biological impact of artificial light, integrating advanced metrics and contemporary interpretation criteria.
The page also explores the functioning of LED sources, the spectral and perceptual implications of solid-state light, the evolution of color rendering criteria, and the growing role of light as an informational and perceptual system, capable of influencing behavior, comfort, and the quality of spatial experience.
Ample space is dedicated to the relevant regulatory and technical framework, international standards, sustainability protocols, and control systems, understood as essential tools for rigorous, measurable, and consistent design.
Overall, the section provides a vision of the theory of light as the cultural and operational basis of lighting design, in which scientific knowledge, perceptual awareness, and design method converge to guide the lighting designer in the construction of balanced, legible, and qualitatively significant spaces.